TSP-5000 Series 1 Installation Guide
Installation Guide
Air Flow Transducer-Actuators
TSP-5000 Series
Mounting
Standard Instructions
The TSP-50xx transducer-actuators are designed to
mount on a standard 1/2" (13 mm) diameter shaft or
a 3/8" (9.5 mm) shaft using the optional HFO-0011
adaptor (see the HFO-0011 Adaptor Instructions
section below).
1. Set the TSP-50xx in the desired location.
2. Slide the TSP-50xx directly on to the 1/2"
diameter damper shaft. The shaft must extend a
minimum of 1-3/4" from the mounting surface.
3. Place the non-rotation bracket (supplied) on the
non-rotation tab.
4. Aachtheanti-rotationbrackettothemounting
surface using #8 or #10 self-tapping screws (not
included).
5. Depressthegeardisengagementbuonand:
a. Rotate the drive hub until the indicator stops
at the “90” mark if the damper is clockwise to
close.
b. Rotate the drive hub to the “0” mark if the
damper is counterclockwise to close.
6. Position the damper to full open.
7. Tighten the two 5/16"-18 hex set screws (see
diagram).
8. Depressthegeardisengagementbuonand
rotate the drive hub/damper to the closed
position.
9. Loosen the adjustable end stop, position it against
the damper position indicator, and retighten it.
HFO-0011 Adaptor Instructions
1. Mount the TSP-5003/23 actuator over the 3/8"
shaft.
2. Slide the HFO-0011 over the shaft into the drive
bushing of the actuator.
3. Align the adaptor slots with the set screws.
4. Tighten the set screws.
Mounting 1
Standard Instructions 1
HFO-0011 Adaptor Instructions 1
Connections and Wiring 2
All Models 2
TSP-5002/5022 Proportional Models 2
TSP-5003/5023 Tri-State Models 2
Setup 3
Calibration 3
Motor Operation Test 3
TSP-5003/5023 Tri-State Models 3
TSP-5002/5022 Proportional Models 3
Accessories 4
Maintenance 4
More Information 4
Important Notices 4
Przeglądanie stron 0
1 2 3 4

Podsumowanie treści

Strona 1 - Installation Guide

TSP-5000 Series 1 Installation GuideInstallation GuideAir Flow Transducer-ActuatorsTSP-5000 Series MountingStandard InstructionsThe TSP-50xx trans

Strona 2 - Connections and Wiring

TSP-5000 Series 2 Installation GuideConnections and WiringAll Models1. Remove the TSP-50xx’s wiring access door by pulling back on the door’s tab a

Strona 3 - Motor Operation Test

TSP-5000 Series 3 Installation GuideSetupThe TSP-50xx is factory calibrated to function with anSSS-1000seriesdierentialpressureowsensor.Usin

Strona 4 - More Information

TSP-5000 Series 4 Installation Guide© 2013 KMC Controls, Inc. 882-019-01xGKMC Controls, Inc.19476 Industrial DriveNew Paris, IN 46553574.831.5250

Komentarze do niniejszej Instrukcji

Brak uwag